OPVC-JZ/OZ-CY


หมวดสินค้า: TKD, Germany

หมวดย่อยสินค้า: เป็นสาย Instument & Control cable: Flexible shield, Unshield, Multicore, Multi-Pair, PVC sheath ทนต่อน้ำมัน, สารเคมี (ให้ดูตาราง)





Application

Power, control and connecting cable in electrical facilities, fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms. Outdoor use only with UV-protection, no laying underground.

Special Feature

  • 4 kV testing voltage
  • no storage outdoors or in wet rooms
  • JZ/OZ: 300/500 V, JB/OB: 0,6/1 kV (from 25 mm²)
  • largely resistant to acids, bases and specified types of oil
  • triple protection for high mechanical requirements and magnetic shield (oxidationproofed steel wire braid and additional inner sheath)

Remarks

  • conform to RoHS
  • conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • LABS-/silicone-free (during production)
  • We are pleased to produce special versions, other dimensions, core and jacket colours on request

Structure and Specifications

  • conductor material : bare copper strand
  • conductor class : acc. to IEC 60228 cl. 5
  • core insulation : PVC
  • core identification : JZ/OZ: acc. to DIN VDE 0293 black cores with white numerals; JB/OB: coloured - up to 5 cores acc. to DIN 293-308, from 6 cores TKD colour code (see technicalguideline) G: with GNYE
  • stranding : stranded in layers
  • inner sheath material : PVC
  • shield : steel wire braid zinced
  • outer sheath : PVC
  • sheath colour : transparent
  • rated voltage : Uo/U - JZ/OZ: 300/500 V || JB/OB: 0,6/1 kV
  • testing voltage : 4 kV
  • conductor resistance : acc. to IEC 60228 cl. 5
  • insulation resistance : min. 20 MΩ x km
  • current carrying capacity : acc. to DIN VDE, see technical Guidelines
  • min. bending radius fixed : 6 x d
  • min. bending radius moved : 15 x d
  • operat. temp. fixed min/max : -30 °C / +80 °C
  • operat. temp. moved min/max : -15 °C / +70 °C
  • temp. at conductor : +70 °C in operation; +150 °C in case of short-circuit
  • burning behavior : self-extinguishing & flame-retardant acc.to IEC 60332-1
  • standard : similar to EN 50525-2-51| 0,6/1 kV-type: with insulation thickness for 1 kV


Download Brochure (PDF file)


 















Home | Company Profile | Certificate | Contact Us
PRIVACY POLICY: SATTELTHAILAND.COM COPYRIGHT © 2011 ALL RIGHTS RESERVED BY SATTELTHAILAND.COM | WEB DESIGN BY WEBCREATIONTEAM.COM